{"data":{"id":"us-mi/mich.-comp.-laws-125.569","jurisdiction":"us-mi","citation":"Mich. Comp. Laws § 125.569","heading":"Metal gauge.","body":"Sec. 19.\n\nThe metal used in all tanks shall be of a minimum gauge, U.S. standard, depending upon the capacity or size as given in the following table:\n\nCapacity Thickness (Gallons) of material 1 to 500 14 gauge 501 to 1100 12 gauge 1101 to 4000 7 gauge 4001 to 10500 1/4 inch 10501 to 20000 5/16 inch 20001 to 30000 3/8 inch\n\nCapacity\n\nThickness\n\n(Gallons)\n\nof material\n\n1 to 500\n\n14 gauge\n\n501 to 1100\n\n12 gauge\n\n1101 to 4000\n\n7 gauge\n\n4001 to 10500\n\n1/4 inch\n\n10501 to 20000\n\n5/16 inch\n\n20001 to 30000\n\n3/8 inch","path":["MI Code","Chapter 125","Act Act-319-of-1929"],"source_url":"https://www.legislature.mi.gov/Laws/MCL?objectName=mcl-125-569","current_through":"2026-08-14","vintage":"open-us-law v2026.08, retrieved 2026-09-14","retrieved_at":"2026-09-14T18:32:31Z","sha256":"90885454e2bb13edd1836a0ca5fa83884040cecb762cceab1667721cd5cff320","source_id":"us-mi","stale":false,"prev":"us-mi/mich.-comp.-laws-125.568","next":"us-mi/mich.-comp.-laws-125.570"},"notice":"GroundRules: Original legal text. Not legal advice."}