{"data":{"id":"us-mi/mich.-comp.-laws-29.5m","jurisdiction":"us-mi","citation":"Mich. Comp. Laws § 29.5m","heading":"Remote control terminal at which tank filled by pipeline; high level alarm system; equipment; sounding of audible trouble alarm.","body":"Sec. 5m.\n\nIn addition to the requirements specified in section 5j, each remote control terminal at which a tank filled by pipeline is located shall be equipped with a high level alarm system which is fail-safe and will provide an audible trouble signal at the remote control point. The audible trouble alarm shall sound upon the occurrence of any of the following:\n\nA loss of the main electrical operating power.\n\nAn electrical break or ground fault in the alarm initiating circuit or the signaling device circuit.\n\nThe derangement of the high level alarm system control equipment.\n\nThe removal of initiating devices.\n\nThe electrical derangement of the signaling devices.","path":["MI Code","Chapter 29","Act Act-207-of-1941"],"source_url":"https://www.legislature.mi.gov/Laws/MCL?objectName=mcl-29-5m","current_through":"2026-08-14","vintage":"open-us-law v2026.08, retrieved 2026-09-14","retrieved_at":"2026-09-14T18:32:31Z","sha256":"efba6613edd69ce27bf48ee604b116471699371c9b1d1a2b6479962f95faceb7","source_id":"us-mi","stale":false,"prev":"us-mi/mich.-comp.-laws-29.5l","next":"us-mi/mich.-comp.-laws-29.5n"},"notice":"GroundRules: Original legal text. Not legal advice."}