{"data":{"id":"us-mi/mich.-comp.-laws-484.2305c","jurisdiction":"us-mi","citation":"Mich. Comp. Laws § 484.2305c","heading":"Emergency power requirements; compliance.","body":"Sec. 305c.\n\nA provider of basic local exchange service shall comply with the following emergency power requirements:\n\n(a) A facilities-based provider shall equip each central office, remote switch, remote line unit, and interexchange toll switching office or access tandem with a minimum of 3 hours of peak load battery reserve, if permanent auxiliary power is installed, and 5 hours of battery reserve, if permanent emergency power is not installed, or 8 hours of battery reserve if the central office is in a remote location. A facilities-based provider shall have available a mobile power unit to be delivered and connected to central offices, remote switches, and remote line units within 8 hours.\n\n(b) An E 9-1-1 service supplier shall provide 24-hour, 7-day-a-week database access to permit information to be acquired or corrected.\n\n(c) A provider, E 9-1-1 service supplier, public safety answering point, or any entity providing or maintaining E 9-1-1 database information shall correct each error in the 9-1-1 system or database within 1 business day.","path":["MI Code","Chapter 484","Act Act-179-of-1991"],"source_url":"https://www.legislature.mi.gov/Laws/MCL?objectName=mcl-484-2305c","current_through":"2026-08-14","vintage":"open-us-law v2026.08, retrieved 2026-09-14","retrieved_at":"2026-09-14T18:32:31Z","sha256":"06f384d600e913b81eee40bfe0645653edc526ddc4673a86ddd0cebfd3f6e16c","source_id":"us-mi","stale":false,"prev":"us-mi/mich.-comp.-laws-484.2305b","next":"us-mi/mich.-comp.-laws-484.2307"},"notice":"GroundRules: Original legal text. Not legal advice."}