{"data":{"id":"us-nyc/n.y.c.-admin.-code-110.26","jurisdiction":"us-nyc","citation":"N.Y.C. Admin. Code § 110.26","heading":"Section 110.26","body":"Section 110.26(A)(1) – Add a new Informational Note at the end of Section 110.26(A)(1) to read as follows:\n\nInformational Note: For Service Rooms or areas with equipment totaling 1,000 kVA or larger, see 230.64 for minimum clearance requirements.\n\nSection 110.26(G) – Add a new Section 110.26(G) to read as follows:\n\n(G) Network Compartments. All network compartments shall have at least 2 means of access. Each door shall access an area that leads to a legal exit.","path":["New York City Administrative Code","Title 28","Chapter 11: The New York City Electrical Code"],"source_url":"https://files.amlegal.com/pdffiles/NewYorkCity/Admin/XML.zip","current_through":"Local Law 2026/135 (enacted August 31, 2026)","vintage":"","retrieved_at":"2026-09-06T02:48:57Z","sha256":"8afe2c5bbf594bde5420e9e40d205866ca70319c24c89088d1a9d11bf8dd0463","source_id":"us-nyc","stale":false,"prev":"us-nyc/n.y.c.-admin.-code-110.11","next":"us-nyc/n.y.c.-admin.-code-110.33"},"notice":"GroundRules: Original legal text. Not legal advice."}