{"data":{"id":"us-nyc/n.y.c.-admin.-code-210.19","jurisdiction":"us-nyc","citation":"N.Y.C. Admin. Code § 210.19","heading":"Section 210.19","body":"Section 210.19(A) – Revise Section 210.19(A) to add a new opening paragraph to read as follows:\n\n(A) Branch Circuits Not More Than 600V. The maximum total voltage drop from the service point to the farthest outlet shall not exceed 5 percent on both feeders and branch circuits combined. Where compliance with the applicable New York City Energy Conservation Code is mandated, the voltage drop requirements of that code shall apply.\n\nSection 210.19(A) – Revise Informational Note No. 3 in Section 210.19(A) to read as follows:\n\nInformational Note No. 3: DELETED.","path":["New York City Administrative Code","Title 28","Chapter 11: The New York City Electrical Code"],"source_url":"https://files.amlegal.com/pdffiles/NewYorkCity/Admin/XML.zip","current_through":"Local Law 2026/135 (enacted August 31, 2026)","vintage":"","retrieved_at":"2026-09-06T02:48:57Z","sha256":"bdab87343a23a73050b40af2a6df5d606ae23e58b2ef8e25560c69495fb35ad8","source_id":"us-nyc","stale":false,"prev":"us-nyc/n.y.c.-admin.-code-210.12","next":"us-nyc/n.y.c.-admin.-code-210.50"},"notice":"GroundRules: Original legal text. Not legal advice."}