{"data":{"id":"us-nyc/n.y.c.-admin.-code-215.2","jurisdiction":"us-nyc","citation":"N.Y.C. Admin. Code § 215.2","heading":"Section 215.2","body":"Section 215.2(A)(1) – Revise the opening paragraph in Section 215.2(A)(1) to read as follows:\n\n(1) General. Feeder conductors shall have an ampacity not less than the larger of 215(A)(1)(a) or (A)(1)(b) and shall comply with 110.14(C). The maximum total voltage drop from the service point to the farthest outlet shall not exceed 5 percent on both feeders and branch circuits combined. The minimum feeder size feeding a dwelling unit shall be 3 conductors with minimum 8 AWG copper or 6 AWG aluminum or copper-clad aluminum conductors. Where compliance with the applicable New York City Energy Conservation Code is mandated, voltage drop requirements of that code shall apply.\n\nSection 215.2(A)(1) – Revise Informational Note No. 2 in Section 215.2(A)(1) to read as follows:\n\nInformational Note No. 2: DELETED.\n\nSection 215.2(A)(1) – Revise Informational Note No. 3 in Section 215.2(A)(1) to read as follows:\n\nInformational Note No. 3: See 210.19(A) for voltage drop for branch circuits.","path":["New York City Administrative Code","Title 28","Chapter 11: The New York City Electrical Code"],"source_url":"https://files.amlegal.com/pdffiles/NewYorkCity/Admin/XML.zip","current_through":"Local Law 2026/135 (enacted August 31, 2026)","vintage":"","retrieved_at":"2026-09-06T02:48:57Z","sha256":"d08d72cb1a584885651b5a4e2c2c4b8042af2eb5765da6c98896cfa353b33845","source_id":"us-nyc","stale":false,"prev":"us-nyc/n.y.c.-admin.-code-210.52","next":"us-nyc/n.y.c.-admin.-code-220.14"},"notice":"GroundRules: Original legal text. Not legal advice."}