{"data":{"id":"us-nyc/n.y.c.-admin.-code-225.30","jurisdiction":"us-nyc","citation":"N.Y.C. Admin. Code § 225.30","heading":"Section 225.30","body":"Section 225.30 – Revise the opening paragraph in Section 225.30 to read as follows:\n\n225.30 Number of Supplies. Where more than 1 building or other structure is on the same property and under single management, each additional building or other structure that is served by a branch circuit or feeder on the load side of a service disconnecting means shall be supplied by only 1 feeder or branch circuit unless permitted in 225.30(A) through (F). For the purpose of this section, a multiwire branch circuit shall be considered a single circuit.","path":["New York City Administrative Code","Title 28","Chapter 11: The New York City Electrical Code"],"source_url":"https://files.amlegal.com/pdffiles/NewYorkCity/Admin/XML.zip","current_through":"Local Law 2026/135 (enacted August 31, 2026)","vintage":"","retrieved_at":"2026-09-06T02:48:57Z","sha256":"bf97519ec4c381e077e40e85363ff05c160704112505e47159417a504fbc61c9","source_id":"us-nyc","stale":false,"prev":"us-nyc/n.y.c.-admin.-code-225.11","next":"us-nyc/n.y.c.-admin.-code-225.31"},"notice":"GroundRules: Original legal text. Not legal advice."}