{"data":{"id":"us-nyc/n.y.c.-admin.-code-230.85","jurisdiction":"us-nyc","citation":"N.Y.C. Admin. Code § 230.85","heading":"Section 230.85","body":"Section 230.85 – Add an Exception at the end of Section 230.85 to read as follows:\n\nException: If the emergency disconnecting means cannot be located in a readily accessible outdoor location, or if the utility metering equipment is located indoors, 1 of the following disconnecting means shall be permitted:\n\n1. A remote disconnecting means provided by the utility\n\n2. An indoor shunt-trip disconnecting means with the control device located in a readily accessible outdoor location and marked, “Remote Emergency Disconnect”\n\n3. An approved equivalent means.","path":["New York City Administrative Code","Title 28","Chapter 11: The New York City Electrical Code"],"source_url":"https://files.amlegal.com/pdffiles/NewYorkCity/Admin/XML.zip","current_through":"Local Law 2026/135 (enacted August 31, 2026)","vintage":"","retrieved_at":"2026-09-06T02:48:57Z","sha256":"cd326d7833cdaa98c11f432594be66032dc355b75c24661b443cd88f6ea4c92b","source_id":"us-nyc","stale":false,"prev":"us-nyc/n.y.c.-admin.-code-230.72","next":"us-nyc/n.y.c.-admin.-code-230.96"},"notice":"GroundRules: Original legal text. Not legal advice."}