{"data":{"id":"us-nyc/n.y.c.-admin.-code-250.35","jurisdiction":"us-nyc","citation":"N.Y.C. Admin. Code § 250.35","heading":"Section 250.35","body":"Section 250.35(B) – Revise Section 250.35(B) to read as follows:\n\n(B) Nonseparately Derived System. If the generator is installed as a nonseparately derived system, and overcurrent protection is not integral with the generator assembly, a supply-side bonding jumper shall be installed between the generator equipment grounding terminal and the equipment grounding terminal, bar, or bus of the disconnecting mean(s). The supply-size bonding jumper shall be sized in accordance with 250.102(C) based on the size of the conductors supplied by the generator. Generators that supply 3 wire loads with no grounded conductor, or 4 wire loads with grounded conductor and supply conductors smaller than what is required in 250.102(C) and 445.13 shall be installed as a separately derived system in accordance with 250.35(A).","path":["New York City Administrative Code","Title 28","Chapter 11: The New York City Electrical Code"],"source_url":"https://files.amlegal.com/pdffiles/NewYorkCity/Admin/XML.zip","current_through":"Local Law 2026/135 (enacted August 31, 2026)","vintage":"","retrieved_at":"2026-09-06T02:48:57Z","sha256":"e025def4eeefdfedf1a7093de4d4ebbc6f024418c894a159136bc7d5a36672d9","source_id":"us-nyc","stale":false,"prev":"us-nyc/n.y.c.-admin.-code-230.96","next":"us-nyc/n.y.c.-admin.-code-250.68"},"notice":"GroundRules: Original legal text. Not legal advice."}