{"data":{"id":"us-nyc/n.y.c.-admin.-code-27-883","jurisdiction":"us-nyc","citation":"N.Y.C. Admin. Code § 27-883","heading":"§ 27-883 Gas equipment connected to chimneys.","body":"Automatically controlled gas-fired equipment connected to a chimney that also serves equipment for the combustion of solid or liquid fuel shall be equipped with an automatic pilot. A gas-fired equipment vent connector and a chimney connector from equipment burning another fuel, located on the same floor, may be connected into the same chimney through separate openings, or may be connected through a single opening if joined by a suitable fitting located as close as practicable to the chimney. If two or more openings are provided into one chimney, they shall be at different levels.","path":["New York City Administrative Code","Title 27","Chapter 1: Building Code"],"source_url":"https://files.amlegal.com/pdffiles/NewYorkCity/Admin/XML.zip","current_through":"Local Law 2026/135 (enacted August 31, 2026)","vintage":"","retrieved_at":"2026-09-06T02:48:57Z","sha256":"ccb03ee5ef55e15ea5d424f2c9835d4bc93c9b7728b3a84f41d5e7bcc19f0e3b","source_id":"us-nyc","stale":false,"prev":"us-nyc/n.y.c.-admin.-code-27-882","next":"us-nyc/n.y.c.-admin.-code-27-884"},"notice":"GroundRules: Original legal text. Not legal advice."}