{"data":{"id":"us-nyc/n.y.c.-admin.-code-27-957","jurisdiction":"us-nyc","citation":"N.Y.C. Admin. Code § 27-957","heading":"§ 27-957 Sprinkler alarm system.","body":"(a) A sprinkler alarm system shall be provided in accordance with the applicable provisions of reference standards RS 17-2, RS 17-2A, RS 17-2B and RS 17-3. Where the building is provided with a class E or modified class E fire alarm signal system, compliance with the applicable provisions of reference standard RS 17-3A or RS 17-3B shall be acceptable in lieu of compliance with provisions of reference standard RS 17-3.\n\n(b) A sprinkler alarm system shall be required when more than thirty-six heads are installed in any fire area or section. See table 17-2 for general requirements.","path":["New York City Administrative Code","Title 27","Chapter 1: Building Code"],"source_url":"https://files.amlegal.com/pdffiles/NewYorkCity/Admin/XML.zip","current_through":"Local Law 2026/135 (enacted August 31, 2026)","vintage":"","retrieved_at":"2026-09-06T02:48:57Z","sha256":"02303c87652005ba1d92d0e9a84da3850d2ce0db9f11c47ccf4aa57ec2c1779a","source_id":"us-nyc","stale":false,"prev":"us-nyc/n.y.c.-admin.-code-27-956","next":"us-nyc/n.y.c.-admin.-code-27-958"},"notice":"GroundRules: Original legal text. Not legal advice."}