{"data":{"id":"us-nyc/n.y.c.-admin.-code-344.10","jurisdiction":"us-nyc","citation":"N.Y.C. Admin. Code § 344.10","heading":"Section 344.10","body":"Section 344.10(A)(2) – Revise Section 344.10(A)(2) to read as follows:\n\n(2) Aluminum RMC. Aluminum RMC shall be permitted to be installed where judged suitable for the environment. Rigid aluminum conduit encased in concrete or in direct contact with the earth shall be provided with listed supplementary corrosion protection.\n\nSection 344.10(B)(2) – Revise Section 344.10(B)(2) to read as follows:\n\n(2) Supplementary Protection of Aluminum RMC. Aluminum RMC shall be provided with listed supplementary corrosion protection where encased in concrete or in direct contact with the earth.","path":["New York City Administrative Code","Title 28","Chapter 11: The New York City Electrical Code"],"source_url":"https://files.amlegal.com/pdffiles/NewYorkCity/Admin/XML.zip","current_through":"Local Law 2026/135 (enacted August 31, 2026)","vintage":"","retrieved_at":"2026-09-06T02:48:57Z","sha256":"5e6df28a471817923aad2bdcce182e02053d93dd7d337801d380a54232a8e7be","source_id":"us-nyc","stale":false,"prev":"us-nyc/n.y.c.-admin.-code-336.104","next":"us-nyc/n.y.c.-admin.-code-350.12"},"notice":"GroundRules: Original legal text. Not legal advice."}
