{"data":{"id":"us-nyc/n.y.c.-admin.-code-352.10","jurisdiction":"us-nyc","citation":"N.Y.C. Admin. Code § 352.10","heading":"Section 352.10","body":"Section 352.10 – Add new Sections 352.10(J) and 352.10(K) to read as follows:\n\n(J) Buildings Not Exceeding 3 Stories. In any building or dwelling unit not exceeding 3 stories above grade.\n\n(K) Buildings Exceeding 3 Stories. Unless prohibited elsewhere by other articles of this code; in any building exceeding 3 stories above grade where the PVC conduit is concealed within non-plenum walls, floors, or ceilings constructed with materials providing a listed 1-hour fire rated assembly or PVC conduit encased in concrete, minimum 2 inches (50.8 mm) thick.","path":["New York City Administrative Code","Title 28","Chapter 11: The New York City Electrical Code"],"source_url":"https://files.amlegal.com/pdffiles/NewYorkCity/Admin/XML.zip","current_through":"Local Law 2026/135 (enacted August 31, 2026)","vintage":"","retrieved_at":"2026-09-06T02:48:57Z","sha256":"355a4c1cf1c30be73262b41842add79019f8eae3e3c5248351f795844664facb","source_id":"us-nyc","stale":false,"prev":"us-nyc/n.y.c.-admin.-code-350.12","next":"us-nyc/n.y.c.-admin.-code-355.10"},"notice":"GroundRules: Original legal text. Not legal advice."}