{"data":{"id":"us-nyc/n.y.c.-admin.-code-362.10","jurisdiction":"us-nyc","citation":"N.Y.C. Admin. Code § 362.10","heading":"Section 362.10","body":"Section 362.10(2) – Revise the opening paragraph of Item (2) in the list of items in Section 362.10 to read as follows:\n\n(2) In any building exceeding 3 floors above grade, ENT shall be concealed within walls, floors, and ceilings where the walls, floors, and ceilings provide a thermal barrier of material that has at least a 1-hour finish rating as identified in listings of fire-rated assemblies. The 1-hour-finish-rated thermal barrier shall be permitted to be used for combustible or noncombustible walls, floors, and ceilings.\n\nSection 362.10(2) – Revise the Exception in Section 362.10(2) to read as follows:\n\nException to (2): DELETED.\n\nSection 362.10(5) – Revise Item (5) in the list of items in Section 362.10 to read as follows:\n\n(5) Above suspended ceilings where the suspended ceilings provide a thermal barrier of material that has at least a 1-hour finish rating as identified in listings of fire-rated assemblies, except as permitted in 362.10(1)(a).\n\nSection 362.10(5) – Revise the Exception at the end of Section 362.10(5) to read as follows:\n\nException to (5): DELETED.","path":["New York City Administrative Code","Title 28","Chapter 11: The New York City Electrical Code"],"source_url":"https://files.amlegal.com/pdffiles/NewYorkCity/Admin/XML.zip","current_through":"Local Law 2026/135 (enacted August 31, 2026)","vintage":"","retrieved_at":"2026-09-06T02:48:57Z","sha256":"707fe0f75369ad16ee384ffcd02c61f1b92191890bca314bf6ae64f57c29276f","source_id":"us-nyc","stale":false,"prev":"us-nyc/n.y.c.-admin.-code-356.12","next":"us-nyc/n.y.c.-admin.-code-362.12"},"notice":"GroundRules: Original legal text. Not legal advice."}