{"data":{"id":"us-nyc/n.y.c.-admin.-code-450.14","jurisdiction":"us-nyc","citation":"N.Y.C. Admin. Code § 450.14","heading":"Section 450.14","body":"Section 450.14 – Revise Section 450.14 to read as follows:\n\n450.14 Disconnecting Means.\n\n(A) Location. Transformers, other than Class 2 or Class 3 transformers, shall have a disconnecting means located either in sight of the transformer or in a remote location. Where located in a remote location, the disconnecting means shall be lockable open in accordance with 110.25, and its location shall be field marked on the transformer.\n\n(B) Rating. For all step-up transformer applications over 225 kVA, the selection of the Primary Disconnect and Step-Up Transformer shall be considered as an engineered system and shall be installed in accordance with 110.3(B) and in compliance with 110.9 and 110.10. The Primary Disconnect device shall be capable of handling the maximum inrush current of the specific transformer being installed. The selection shall be made by a registered design professional engaged primarily in the design, installation, or maintenance of electrical systems. The selection shall be documented and made available to those authorized to design, install, inspect, maintain, and operate the system.","path":["New York City Administrative Code","Title 28","Chapter 11: The New York City Electrical Code"],"source_url":"https://files.amlegal.com/pdffiles/NewYorkCity/Admin/XML.zip","current_through":"Local Law 2026/135 (enacted August 31, 2026)","vintage":"","retrieved_at":"2026-09-06T02:48:57Z","sha256":"dd9a47da90f17030e13905953715a60d0e7a242ec52ea8eeac44c23ba8b8a3e2","source_id":"us-nyc","stale":false,"prev":"us-nyc/n.y.c.-admin.-code-445.10","next":"us-nyc/n.y.c.-admin.-code-450.25"},"notice":"GroundRules: Original legal text. Not legal advice."}