{"data":{"id":"us-nyc/n.y.c.-admin.-code-517.31","jurisdiction":"us-nyc","citation":"N.Y.C. Admin. Code § 517.31","heading":"Section 517.31","body":"Section 517.31(C)(3)(1) – Revise Item (1) in the list of items in Section 517.31(C)(3) to read as follows:\n\n(1) \n\t\t\t\t\t\t\t\t\t\t\t\tNonflexible metal raceways, Type MI cable, or Type RTRC marked with the suffix –XW. Nonmetallic raceways shall not be used for branch circuits that supply patient care areas.\n\nSection 517.31(C)(4) – Add a new Section 517.31(C)(4) to read as follows:\n\n(4) Generator Control Wiring. Control conductors installed between the transfer equipment and the emergency generator shall be kept entirely independent of all other wiring and shall meet the conditions of 700.10(D)(1).","path":["New York City Administrative Code","Title 28","Chapter 11: The New York City Electrical Code"],"source_url":"https://files.amlegal.com/pdffiles/NewYorkCity/Admin/XML.zip","current_through":"Local Law 2026/135 (enacted August 31, 2026)","vintage":"","retrieved_at":"2026-09-06T02:48:57Z","sha256":"f245656fa67712daa0151d2f1f30fe0ae813feea608ea0d045ca32aca545dd47","source_id":"us-nyc","stale":false,"prev":"us-nyc/n.y.c.-admin.-code-517.30","next":"us-nyc/n.y.c.-admin.-code-517.32"},"notice":"GroundRules: Original legal text. Not legal advice."}