{"data":{"id":"us-nyc/n.y.c.-admin.-code-517.43","jurisdiction":"us-nyc","citation":"N.Y.C. Admin. Code § 517.43","heading":"Section 517.43","body":"Section 517.43 – Revise the title and first paragraph of Section 517.43 to read as follows:\n\n517.43 Automatic Connection to Life Safety Branch. The life safety branch shall be installed and connected to the alternate source of power specified in 517.41 so that all functions specified herein for the life safety branch are automatically restored to operation within 10 seconds after interruption of the normal source.","path":["New York City Administrative Code","Title 28","Chapter 11: The New York City Electrical Code"],"source_url":"https://files.amlegal.com/pdffiles/NewYorkCity/Admin/XML.zip","current_through":"Local Law 2026/135 (enacted August 31, 2026)","vintage":"","retrieved_at":"2026-09-06T02:48:57Z","sha256":"717884901bd707178c9cc95292d253d2c50a698735ad7cee034a98d91e38a4d1","source_id":"us-nyc","stale":false,"prev":"us-nyc/n.y.c.-admin.-code-517.32","next":"us-nyc/n.y.c.-admin.-code-517.44"},"notice":"GroundRules: Original legal text. Not legal advice."}