{"data":{"id":"us-nyc/n.y.c.-admin.-code-517.44","jurisdiction":"us-nyc","citation":"N.Y.C. Admin. Code § 517.44","heading":"Section 517.44","body":"Section 517.44 – Revise the opening paragraph in Section 517.44 to read as follows:\n\n517.44 Connection to Equipment Branch. The equipment branch shall be installed and connected to the alternate power source such that equipment described in 517.44(A) is automatically restored to operation at appropriate time-lag intervals following the energizing of the life safety branch. {99:6.7.5.l.4.2(A)}\n\nSection 517.44(B) – Revise Item (3) in the list of items in Section 517.44(B) to read as follows:\n\n(3) Optional Connections to the Equipment Branch. Additional illumination, receptacles, and equipment shall be permitted to be connected only to the equipment branch.","path":["New York City Administrative Code","Title 28","Chapter 11: The New York City Electrical Code"],"source_url":"https://files.amlegal.com/pdffiles/NewYorkCity/Admin/XML.zip","current_through":"Local Law 2026/135 (enacted August 31, 2026)","vintage":"","retrieved_at":"2026-09-06T02:48:57Z","sha256":"e48c9c14af2f5651c0c0d34a4d895e9add271537661077d60cd30f9516207057","source_id":"us-nyc","stale":false,"prev":"us-nyc/n.y.c.-admin.-code-517.43","next":"us-nyc/n.y.c.-admin.-code-518.1"},"notice":"GroundRules: Original legal text. Not legal advice."}