{"data":{"id":"us-nyc/n.y.c.-admin.-code-695.14","jurisdiction":"us-nyc","citation":"N.Y.C. Admin. Code § 695.14","heading":"Section 695.14","body":"Section 695.14(E)– Revise Section 695.14(E) to read as follows:\n\n(E) Electric Fire Pump Control Wiring Methods. All electric motor-driven fire pump control wiring shall be in rigid metal conduit, intermediate metal conduit, or electrical metallic tubing with watertight fittings.\n\nSection 695.14(F) – Add exception at the end of Section 695.14(F) to read as follows:\n\nException to 695.14(F)(1) and (F)(2): The control conductors located in the electrical equipment room where they originate and in the fire pump room shall not be required to have the minimum 2-hour fire separation or fire resistance rating.","path":["New York City Administrative Code","Title 28","Chapter 11: The New York City Electrical Code"],"source_url":"https://files.amlegal.com/pdffiles/NewYorkCity/Admin/XML.zip","current_through":"Local Law 2026/135 (enacted August 31, 2026)","vintage":"","retrieved_at":"2026-09-06T02:48:57Z","sha256":"99014d8a89a163cb2c918400eb6dae83254de798c9348e3b1996b53ca27bdb63","source_id":"us-nyc","stale":false,"prev":"us-nyc/n.y.c.-admin.-code-695.6","next":"us-nyc/n.y.c.-admin.-code-700.1"},"notice":"GroundRules: Original legal text. Not legal advice."}