{"data":{"id":"us-nyc/n.y.c.-admin.-code-700.11","jurisdiction":"us-nyc","citation":"N.Y.C. Admin. Code § 700.11","heading":"Section 700.11","body":"Section 700.11 – Add a new Section 700.11 to read as follows:\n\n700.11 Generator Supply Conductors without Overcurrent Protection.\n\n(A) Conductors Ampacity. See 445.13 of this code.\n\n(B) Installation of Generator Conductors. Conductors from the generator output terminal to the first overcurrent device shall be installed in accordance with 230.6.\n\n(C) Overcurrent Devices. The number of overcurrent devices supplied by the generator shall not be limited.","path":["New York City Administrative Code","Title 28","Chapter 11: The New York City Electrical Code"],"source_url":"https://files.amlegal.com/pdffiles/NewYorkCity/Admin/XML.zip","current_through":"Local Law 2026/135 (enacted August 31, 2026)","vintage":"","retrieved_at":"2026-09-06T02:48:57Z","sha256":"9a772e5cf40510c1a0e85da7415e6be8f5d714bf42503de57308f2fb3cd0d2eb","source_id":"us-nyc","stale":false,"prev":"us-nyc/n.y.c.-admin.-code-700.10","next":"us-nyc/n.y.c.-admin.-code-700.12"},"notice":"GroundRules: Original legal text. Not legal advice."}