{"data":{"id":"us-nyc/n.y.c.-admin.-code-725.48","jurisdiction":"us-nyc","citation":"N.Y.C. Admin. Code § 725.48","heading":"Section 725.48","body":"Section 725.48(B)(1) – Revise Section 725.48(B)(1) to read as follows:\n\n(1) In a Cable, Enclosure, or Raceway. Class 1 circuits and power-supply circuits shall be permitted to occupy the same cable, enclosure, or raceway without a barrier only where the equipment powered is functionally associated. Class I circuits shall be permitted to be installed together with the conductors of electric light, power, and medium power network-powered broadband communications circuits where separated by a barrier.","path":["New York City Administrative Code","Title 28","Chapter 11: The New York City Electrical Code"],"source_url":"https://files.amlegal.com/pdffiles/NewYorkCity/Admin/XML.zip","current_through":"Local Law 2026/135 (enacted August 31, 2026)","vintage":"","retrieved_at":"2026-09-06T02:48:57Z","sha256":"71559f33805641611767d384c814cbd8a24f73c94198424fbb07bb546e8f95ca","source_id":"us-nyc","stale":false,"prev":"us-nyc/n.y.c.-admin.-code-725.25","next":"us-nyc/n.y.c.-admin.-code-725.136"},"notice":"GroundRules: Original legal text. Not legal advice."}