{"data":{"id":"us-nyc/n.y.c.-admin.-code-760.33","jurisdiction":"us-nyc","citation":"N.Y.C. Admin. Code § 760.33","heading":"Section 760.33","body":"Section 760.33 – Add a new Section 760.33 to read as follows:\n\n760.33 Fire Alarm System and Equipment Grounding. Fire alarm system and equipment grounding shall be installed in accordance with the following:\n\n(A) Grounding Electrode Conductor. Each service or separately derived system supplying a fire alarm system shall be provided with a separate grounding electrode conductor originating at any point on the building grounding electrode system and sized and installed in accordance with Part III of Article 250.\n\n(B) Equipment Grounding Conductor. Where there are conduits supplying 120V to the fire command center, control unit, or distributed control cabinets, a separate green insulated equipment grounding conductor shall be sized and installed in accordance with Article 250, Table 250.122.","path":["New York City Administrative Code","Title 28","Chapter 11: The New York City Electrical Code"],"source_url":"https://files.amlegal.com/pdffiles/NewYorkCity/Admin/XML.zip","current_through":"Local Law 2026/135 (enacted August 31, 2026)","vintage":"","retrieved_at":"2026-09-06T02:48:57Z","sha256":"90549bb47adf8d410cf1a523c72b8b391b247e7cac914f2d3e833abdcc2b979a","source_id":"us-nyc","stale":false,"prev":"us-nyc/n.y.c.-admin.-code-760.32","next":"us-nyc/n.y.c.-admin.-code-760.41"},"notice":"GroundRules: Original legal text. Not legal advice."}