{"data":{"id":"us-nyc/n.y.c.-admin.-code-760.46","jurisdiction":"us-nyc","citation":"N.Y.C. Admin. Code § 760.46","heading":"Section 760.46","body":"Section 760.46 – Revise Section 760.46 to read as follows:\n\n760.46 NPLFA Circuit Wiring. Installation of non-power limited fire alarm feeders and branch circuits shall be in accordance with applicable portions of 110.3(B), 300.7, 300.11, 300.15, 300.17, 300.19(B) and other appropriate articles of Chapter 3 using raceway methods described in Articles 342, 344, and 358, or use Type MI Cable in accordance with Article 332. For the last 3 ft (914 mm) of NPLFA branch circuit, a Flexible Metallic Conduit (FMC) or Liquidtight Flexible Metallic Conduit (LFMC) shall be permitted.\n\nException No. 1: As provided in 760.48 through 760.52.\n\nException No. 2: This section does not apply where other articles of this Code require other methods.\n\nException No. 3: Where other articles of this code require other wiring to be used, a listed electrical protective system with minimum 2-hour fire rating shall be permitted.","path":["New York City Administrative Code","Title 28","Chapter 11: The New York City Electrical Code"],"source_url":"https://files.amlegal.com/pdffiles/NewYorkCity/Admin/XML.zip","current_through":"Local Law 2026/135 (enacted August 31, 2026)","vintage":"","retrieved_at":"2026-09-06T02:48:57Z","sha256":"c437c5122ef152b025cb62105657657474fd3e187785853fd3b21d03001e0d00","source_id":"us-nyc","stale":false,"prev":"us-nyc/n.y.c.-admin.-code-760.43","next":"us-nyc/n.y.c.-admin.-code-760.48"},"notice":"GroundRules: Original legal text. Not legal advice."}