{"data":{"id":"us-nyc/n.y.c.-admin.-code-760.48","jurisdiction":"us-nyc","citation":"N.Y.C. Admin. Code § 760.48","heading":"Section 760.48","body":"Section 760.48 – Revise Section 760.48(A) to read as follows:\n\n760.48 Conductors of Different Circuits in Same Cable, Enclosure, or Raceway.\n\n(A) NPLFA Circuits. Non-power limited fire alarm circuit conductors shall not be permitted to occupy the same cable, enclosure, or raceway with circuit conductors of other systems.\n\nSection 760.48 – Revise Section 760.48(B) to read as follows:\n\n(B) Fire Alarm with Power-Supply Circuits. Power supply and fire alarm circuit conductors shall be permitted in the same enclosure only where connected to the same equipment.","path":["New York City Administrative Code","Title 28","Chapter 11: The New York City Electrical Code"],"source_url":"https://files.amlegal.com/pdffiles/NewYorkCity/Admin/XML.zip","current_through":"Local Law 2026/135 (enacted August 31, 2026)","vintage":"","retrieved_at":"2026-09-06T02:48:57Z","sha256":"1c4e1f41706c94cc0d6919836376d503bf048bbf4c1f8abf3a91f980cbc45cd1","source_id":"us-nyc","stale":false,"prev":"us-nyc/n.y.c.-admin.-code-760.46","next":"us-nyc/n.y.c.-admin.-code-760.49"},"notice":"GroundRules: Original legal text. Not legal advice."}