{"data":{"id":"us-nyc/n.y.c.-admin.-code-770.100","jurisdiction":"us-nyc","citation":"N.Y.C. Admin. Code § 770.100","heading":"Section 770.100","body":"Section 770.100(B)(3)(2) – Revise Section 770.100(B)(3)(2) to read as follows:\n\n(2) If the building or structure served has no grounding means, as described in 770.100(B)(2) or (B)(3)(1), to any one of the individual grounding electrodes described in 250.52(A)(7) and (A)(8) or to a ground rod or pipe not less than 5 ft (1.5 m) in length and 1/2 in. (12.7 mm) in diameter, driven, where practicable, into permanently damp earth and separated from lightning protection system conductors as covered in 800.53 and at least 6 ft (1.8 m) from electrodes of other systems. Steam, hot water pipes, or lightning protection system conductors shall not be employed as electrodes for non-current-carrying metallic members.","path":["New York City Administrative Code","Title 28","Chapter 11: The New York City Electrical Code"],"source_url":"https://files.amlegal.com/pdffiles/NewYorkCity/Admin/XML.zip","current_through":"Local Law 2026/135 (enacted August 31, 2026)","vintage":"","retrieved_at":"2026-09-06T02:48:57Z","sha256":"24807f5bdbf8cf0d3d0f040e6305600e4cf9ca1767356f34401ed5981403d961","source_id":"us-nyc","stale":false,"prev":"us-nyc/n.y.c.-admin.-code-770.48","next":"us-nyc/n.y.c.-admin.-code-770.133"},"notice":"GroundRules: Original legal text. Not legal advice."}