{"data":{"id":"us-nyc/n.y.c.-admin.-code-800.24","jurisdiction":"us-nyc","citation":"N.Y.C. Admin. Code § 800.24","heading":"Section 800.24","body":"Section 800.24 – Revise the opening paragraph in Section 800.24 to read as follows:\n\n800.24 Mechanical Execution of Work. Circuits and equipment shall be installed in a neat and workmanlike manner. Cables installed exposed on the surface of ceilings and sidewalls shall be supported by approved non-combustible straps, staples, cable ties, hangers, or similar fittings and related installation accessories designed and installed so as not to damage the cables. The installation shall also conform to 300.4 and 300.11. Nonmetallic cable ties and other nonmetallic cable accessories used to secure and support cables in other spaces used for environmental air (plenums) shall be listed as having low smoke and heat release properties in accordance with 805.170(C).\n\nSection 800.24 – Add a new Informational Note in Section 800.24 to read as follows:\n\nInformational Note No. 4: Exposed wiring should be securely held in place to avoid entanglement of fire response personnel during fire conditions.","path":["New York City Administrative Code","Title 28","Chapter 11: The New York City Electrical Code"],"source_url":"https://files.amlegal.com/pdffiles/NewYorkCity/Admin/XML.zip","current_through":"Local Law 2026/135 (enacted August 31, 2026)","vintage":"","retrieved_at":"2026-09-06T02:48:57Z","sha256":"aa967965983d0a5a35d0609e278191d34998411d6799bce24a1528970752e5a5","source_id":"us-nyc","stale":false,"prev":"us-nyc/n.y.c.-admin.-code-770.133","next":"us-nyc/n.y.c.-admin.-code-800.25"},"notice":"GroundRules: Original legal text. Not legal advice."}