{"data":{"id":"us-nyc/n.y.c.-admin.-code-fc-2506","jurisdiction":"us-nyc","citation":"N.Y.C. Admin. Code § FC 2506","heading":"Section FC 2506: Ethylene Generators","body":"2506.1 Ethylene generators.\n\nEthylene generators shall be listed and labeled by an approved testing laboratory and used only in approved rooms in accordance with the ethylene generator manufacturer's instructions. The listing evaluation shall include documentation that the concentration of ethylene gas does not exceed 25 percent of the lower explosive limit (LEL).\n\n2506.2 Ethylene generator rooms.\n\nEthylene generators shall be used in rooms having a volume of not less than the minimum room size provided for in the manufacturer's specifications and testing laboratory listing, but in no case less than 1,000 cubic feet (28 m\n\t\t\t\t\t\t\t\t\t\t\t\t\t\n\t\t\t\t\t\t\t\t\t\t\t\t\t3\n\t\t\t\t\t\t\t\t\t\t\t\t\t\n\t\t\t\t\t\t\t\t\t\t\t\t\t\n\t\t\t\t\t\t\t\t\t\t\t\t\t). Rooms shall have air circulation to ensure even distribution of ethylene gas and shall be free from sparks, open flames or other ignition sources.","path":["New York City Administrative Code","Title 29","Chapter 2: New York City Fire Code"],"source_url":"https://files.amlegal.com/pdffiles/NewYorkCity/Admin/XML.zip","current_through":"Local Law 2026/135 (enacted August 31, 2026)","vintage":"","retrieved_at":"2026-09-06T02:48:57Z","sha256":"bcd8fbc15d6fc1113796617ef305bdf451539011220b58fb1bd8168206610935","source_id":"us-nyc","stale":true,"prev":"us-nyc/n.y.c.-admin.-code-fc-2505","next":"us-nyc/n.y.c.-admin.-code-fc-2507"},"notice":"GroundRules: Original legal text. Not legal advice."}