{"data":{"id":"us-nyc/n.y.c.-admin.-code-fc-3307","jurisdiction":"us-nyc","citation":"N.Y.C. Admin. Code § FC 3307","heading":"Section FC 3307: Explosive Materials","body":"3307.1 Storage and handling.\n\nExplosive materials shall be stored, handled and used in accordance with FC 3318 and FC Chapter 56.\n\n3307.2 Blasting operations.\n\nBlasting operations shall be conducted in accordance with FC Chapter 56.\n\n3307.3 Demolition using explosives.\n\nFire hoses and nozzles for use by demolition personnel, connected to an approved water supply under pressure, shall be provided and maintained at the demolition site whenever explosives are used for demolition. Such fire hoses, nozzles and water supply shall be available prior to explosives arriving at the site. Such fire hoses and nozzles shall be capable of a continuous flow of 180 gallons (681 L) per minute with a minimum reach of 35 feet (10 668 mm) from the nozzle and be capable of being brought to bear anywhere on the construction site. Hose shall be pressure tested to withstand at least 600 pounds per square inch gauge (psig) (2413 kPa).","path":["New York City Administrative Code","Title 29","Chapter 2: New York City Fire Code"],"source_url":"https://files.amlegal.com/pdffiles/NewYorkCity/Admin/XML.zip","current_through":"Local Law 2026/135 (enacted August 31, 2026)","vintage":"","retrieved_at":"2026-09-06T02:48:57Z","sha256":"3ff463b4e994708d2eba32235372c8d4b6a3ccc09ce59252cfcf00e085804c96","source_id":"us-nyc","stale":true,"prev":"us-nyc/n.y.c.-admin.-code-fc-3306","next":"us-nyc/n.y.c.-admin.-code-fc-3308"},"notice":"GroundRules: Original legal text. Not legal advice."}