{"data":{"id":"us-nyc/n.y.c.-admin.-code-fgc-310","jurisdiction":"us-nyc","citation":"N.Y.C. Admin. Code § FGC 310","heading":"Section FGC 310: Electrical Bonding","body":"310.1 Pipe and tubing.\n\nEach above-ground portion of a gas piping system that is likely to become energized shall be continuously bonded electrically to an effective ground-fault current path. Gas piping shall be considered to be bonded where it is connected to appliances that are connected to the equipment grounding conductor of the circuit supplying that appliance.","path":["New York City Administrative Code","Title 28","Chapter 9: New York City Fuel Gas Code"],"source_url":"https://files.amlegal.com/pdffiles/NewYorkCity/Admin/XML.zip","current_through":"Local Law 2026/135 (enacted August 31, 2026)","vintage":"","retrieved_at":"2026-09-06T02:48:57Z","sha256":"639885a0d81311131169fd4221b0d8b5aef2a04a37d9aa6f739a9d6122c3046a","source_id":"us-nyc","stale":false,"prev":"us-nyc/n.y.c.-admin.-code-fgc-309","next":"us-nyc/n.y.c.-admin.-code-fgc-401"},"notice":"GroundRules: Original legal text. Not legal advice."}