{"data":{"id":"us-nyc/n.y.c.-admin.-code-fgc-625","jurisdiction":"us-nyc","citation":"N.Y.C. Admin. Code § FGC 625","heading":"Section FGC 625: Refrigerators","body":"625.1 General.\n\nRefrigerators shall be tested in accordance with ANSI Z21.19/CSA 1.4 and shall be installed in accordance with the manufacturer's instructions.\n\nRefrigerators shall be provided with adequate clearances for ventilation at the top and back, and shall be installed in accordance with the manufacturer's instructions. If such instructions are not available, not less than 2 inches (50.8 mm) shall be provided between the back of the refrigerator and the wall and not less than 12 inches (304.8 mm) above the top.","path":["New York City Administrative Code","Title 28","Chapter 9: New York City Fuel Gas Code"],"source_url":"https://files.amlegal.com/pdffiles/NewYorkCity/Admin/XML.zip","current_through":"Local Law 2026/135 (enacted August 31, 2026)","vintage":"","retrieved_at":"2026-09-06T02:48:57Z","sha256":"2a88fd272ed902390ac06b2d9ba06f47e8c6042bce4126b1b120a9f2b0dfa97c","source_id":"us-nyc","stale":false,"prev":"us-nyc/n.y.c.-admin.-code-fgc-624","next":"us-nyc/n.y.c.-admin.-code-fgc-626"},"notice":"GroundRules: Original legal text. Not legal advice."}