{"data":{"id":"us-nyc/n.y.c.-admin.-code-mc-1005","jurisdiction":"us-nyc","citation":"N.Y.C. Admin. Code § MC 1005","heading":"Section MC 1005: Boiler Connections","body":"1005.1 Valves.\n\nEvery boiler or modular boiler shall have a shutoff valve in the supply and return piping. For multiple boiler or multiple modular boiler installations, each boiler or modular boiler shall have individual shutoff valves in the supply and return piping.\n\nException: Shutoff valves are not required in a system having a single low-pressure steam boiler of 350,000 Btu/h (103 kW) output or less.\n\n1005.2 Potable water supply.\n\nThe water supply to all boilers, including but not limited to backflow prevention, shall be connected in accordance with the New York City Plumbing Code.","path":["New York City Administrative Code","Title 28","Chapter 8: New York City Mechanical Code"],"source_url":"https://files.amlegal.com/pdffiles/NewYorkCity/Admin/XML.zip","current_through":"Local Law 2026/135 (enacted August 31, 2026)","vintage":"","retrieved_at":"2026-09-06T02:48:57Z","sha256":"8eedcbf69088d65e12bfc109ef377e37ab5ddcd17fe659579e8028b5c0d84667","source_id":"us-nyc","stale":false,"prev":"us-nyc/n.y.c.-admin.-code-mc-1004","next":"us-nyc/n.y.c.-admin.-code-mc-1006"},"notice":"GroundRules: Original legal text. Not legal advice."}