{"data":{"id":"us-nyc/n.y.c.-admin.-code-mc-1208","jurisdiction":"us-nyc","citation":"N.Y.C. Admin. Code § MC 1208","heading":"Section MC 1208: Tests","body":"1208.1 General.\n\nHydronic piping systems other than ground-source heat pump loop systems shall be tested hydrostatically at one and one half times the system design operating pressure, but not less than 100 psi (689 kPa). The duration of each test shall be not less than 2 hours. Ground-source heat pump loop systems shall be tested in accordance with Section 1210.10.","path":["New York City Administrative Code","Title 28","Chapter 8: New York City Mechanical Code"],"source_url":"https://files.amlegal.com/pdffiles/NewYorkCity/Admin/XML.zip","current_through":"Local Law 2026/135 (enacted August 31, 2026)","vintage":"","retrieved_at":"2026-09-06T02:48:57Z","sha256":"e17a4f4e73cd2918cc00d153126dc786022bd25c5b4e09d87a7f8346ae784a29","source_id":"us-nyc","stale":false,"prev":"us-nyc/n.y.c.-admin.-code-mc-1207","next":"us-nyc/n.y.c.-admin.-code-mc-1209"},"notice":"GroundRules: Original legal text. Not legal advice."}