{"data":{"id":"us-nyc/n.y.c.-admin.-code-mc-1403","jurisdiction":"us-nyc","citation":"N.Y.C. Admin. Code § MC 1403","heading":"Section MC 1403: Heat Transfer Fluids","body":"1403.1 Flash point.\n\nThe flash point of the actual heat transfer fluid utilized in a solar system shall be not less than 50°F (10°C) above the design maximum nonoperating (no-flow) temperature of the fluid attained in the collector.\n\n1403.2 Flammable gases and liquids.\n\nA flammable liquid or gas shall not be utilized as a heat transfer fluid.","path":["New York City Administrative Code","Title 28","Chapter 8: New York City Mechanical Code"],"source_url":"https://files.amlegal.com/pdffiles/NewYorkCity/Admin/XML.zip","current_through":"Local Law 2026/135 (enacted August 31, 2026)","vintage":"","retrieved_at":"2026-09-06T02:48:57Z","sha256":"3dfd915905b990a7d289b2494ecd6f44a96edd89f8925eb1f497d7a3850ec864","source_id":"us-nyc","stale":false,"prev":"us-nyc/n.y.c.-admin.-code-mc-1402","next":"us-nyc/n.y.c.-admin.-code-mc-1404"},"notice":"GroundRules: Original legal text. Not legal advice."}