{"data":{"id":"us-nyc/n.y.c.-admin.-code-pc-711","jurisdiction":"us-nyc","citation":"N.Y.C. Admin. Code § PC 711","heading":"Section PC 711: Offsets In Drainage Piping In Buildings of Five Stories or More","body":"711.1 Horizontal branch connections above or below vertical stack offsets.\n\nIf a horizontal branch connects to the stack within 2 feet (610 mm) above or below a vertical stack offset, and the offset is located more than four branch intervals below the top of the stack, the offset shall be vented in accordance with Section \n\t\t\t\t\t\t\t\t\t\t\t\t\t\n\t\t\t\t\t\t\t\t\t\t\t\t\t\t907\n\t\t\t\t\t\t\t\t\t\t\t\t\t\n\t\t\t\t\t\t\t\t\t\t\t\t\t.\n\n711.1.1 Omission of vents for vertical stack offsets.\n\nVents for vertical offsets required by Section 711.1 shall not be required where the stack and its offset are sized as a building drain (see \n\t\t\t\t\t\t\t\t\t\t\t\t\t\n\t\t\t\t\t\t\t\t\t\t\t\t\t\tTable 710.1(1)\n\t\t\t\t\t\t\t\t\t\t\t\t\t\n\t\t\t\t\t\t\t\t\t\t\t\t\t, Column 5).\n\n711.2 Horizontal stack offsets.\n\nA stack with a horizontal offset located more than four branch intervals below the top of the stack shall be vented in accordance with Section \n\t\t\t\t\t\t\t\t\t\t\t\t\t\n\t\t\t\t\t\t\t\t\t\t\t\t\t\t907\n\t\t\t\t\t\t\t\t\t\t\t\t\t\n\t\t\t\t\t\t\t\t\t\t\t\t\t and sized as follows:\n\n1. The portion of the stack above the offset shall be sized as for a vertical stack based on the total number of drainage fixture units above the offset.\n\n2. The offset shall be sized in accordance with Section 710.1.1.\n\n3. The portion of the stack below the offset shall be sized as for the offset or based on the total number of drainage fixture units on the entire stack, whichever is larger (see \n\t\t\t\t\t\t\t\t\t\t\t\t\t\n\t\t\t\t\t\t\t\t\t\t\t\t\t\tTable 710.1(2)\n\t\t\t\t\t\t\t\t\t\t\t\t\t\n\t\t\t\t\t\t\t\t\t\t\t\t\t, Column 4).\n\n711.2.1 Omission of vents for horizontal stack offsets.\n\nVents for horizontal stack offsets required by Section 711.2 shall not be required where the stack and its offset are one pipe size larger than required for a building drain (see \n\t\t\t\t\t\t\t\t\t\t\t\t\t\n\t\t\t\t\t\t\t\t\t\t\t\t\t\tTable 710.1(1)\n\t\t\t\t\t\t\t\t\t\t\t\t\t\n\t\t\t\t\t\t\t\t\t\t\t\t\t, Column 5) and the entire stack and offset are not less in cross- sectional area than that required for a straight stack plus the area of an offset vent as provided for in Section \n\t\t\t\t\t\t\t\t\t\t\t\t\t\n\t\t\t\t\t\t\t\t\t\t\t\t\t\t907\n\t\t\t\t\t\t\t\t\t\t\t\t\t\n\t\t\t\t\t\t\t\t\t\t\t\t\t.\n\n711.3 Offsets below lowest branch.\n\nWhere a vertical offset occurs in a soil or waste stack below the lowest horizontal branch, a change in diameter of the stack because of the offset shall not be required. If a horizontal offset occurs in a soil or waste stack below the lowest horizontal branch, the required diameter of the offset and the stack below it shall be determined as for a building drain in accordance with \n\t\t\t\t\t\t\t\t\t\t\t\t\t\n\t\t\t\t\t\t\t\t\t\t\t\t\t\tTable 710.1(1)\n\t\t\t\t\t\t\t\t\t\t\t\t\t\n\t\t\t\t\t\t\t\t\t\t\t\t\t.","path":["New York City Administrative Code","Title 28","Chapter 6: New York City Plumbing Code"],"source_url":"https://files.amlegal.com/pdffiles/NewYorkCity/Admin/XML.zip","current_through":"Local Law 2026/135 (enacted August 31, 2026)","vintage":"","retrieved_at":"2026-09-06T02:48:57Z","sha256":"93bdd5a7dbc8652ab33fbf1ee06ca299b60a02d546f74c47def897a5672a3aff","source_id":"us-nyc","stale":false,"prev":"us-nyc/n.y.c.-admin.-code-pc-710","next":"us-nyc/n.y.c.-admin.-code-pc-712"},"notice":"GroundRules: Original legal text. Not legal advice."}