{"data":{"id":"us-va/16vac25-50-430","jurisdiction":"us-va","citation":"16VAC25-50-430","heading":"Hydrostatic pressure tests","body":"A. A hydrostatic pressure test, when applied to boilers or pressure vessels, shall not exceed 1.25 times the maximum allowable working pressure, except as provided by the current edition of the ASME Code. The pressure shall be under proper control so that in no case shall the required test pressure be exceeded by more than 2.0%.\n\nB. See 16VAC25-50-360 A 4 for temperature limitations on particular power boiler installations.\n\nC. When a hydrostatic test is to be applied to existing installations, the pressure shall be as follows:\n\n1. For all cases involving the question of tightness, the pressure shall be equal to the working pressure.\n\n2. For all cases involving the question of safety, the test pressure shall not exceed 1.25 times the maximum allowable working pressure for temperature. During such test the safety valve or valves shall be removed or each valve disk shall be held to its seat by means of a testing clamp and not by screwing down the compression screw upon the spring.","path":["Title 16. Labor And Employment","Agency 25. Safety And Health Codes Board","Chapter 50. Boiler and Pressure Vessel Regulations","Part IV. General Requirements"],"source_url":"https://law.lis.virginia.gov/admincode/title16/agency25/chapter50/section430/","current_through":"2026 Regular Session (effective July 1, 2026)","vintage":"","retrieved_at":"2026-09-14T04:52:08Z","sha256":"36acd96b38a1590879b147bafb95f8aa684a81add5abfd21d06ba54e1e3ed0f3","source_id":"us-va-vac","stale":false,"prev":"us-va/16vac25-50-420","next":"us-va/16vac25-50-440"},"notice":"GroundRules: Original legal text. Not legal advice."}