{"data":{"id":"us/10-cfr-434.513","jurisdiction":"us","citation":"10 CFR 434.513","heading":"Occupancy.","body":"5131 Occupancy schedules are default assumptions. The same assumptions shall be made in computing Design Energy Consumption as were used in calculating the Energy Cost Budget.\n513.2 Table 513.2.a, Occupancy Density, establishes the density, in ft 2 person of conditioned floor area, to be used for each building type. Table 513.2.b, Building Schedule Percentage Multipliers, establishes the percentage of total occupants in the building by hour of the day for each building type.\nTable 513.2. a—Occupancy Density\nBuilding type Conditioned floor area Ft 2 person\nAssembly 50\nOffice 275\nRetail 300\nWarehouse 15000\nSchool 75\nHotel/Motel 250\nRestaurant 100\nHealth/Institutional 200\nMulti-family High-rise Residential 2 per unit . 1\n1 Heat generation: Btu/h per person: 230 Btu/h per person sensible, and 190 Btu/h per person latent. See Tables 512.2 a and b.","path":["Title 10—Energy","CHAPTER II—DEPARTMENT OF ENERGY","SUBCHAPTER D—ENERGY CONSERVATION","PART 434—ENERGY CODE FOR NEW FEDERAL COMMERCIAL AND MULTI-FAMILY HIGH RISE RESIDENTIAL BUILDINGS","Subpart E—Building Energy Cost Compliance Alternative"],"source_url":"https://www.ecfr.gov/api/versioner/v1/full/2026-08-25/title-10.xml","current_through":"2026-08-25","vintage":"","retrieved_at":"2026-08-27T02:24:09Z","sha256":"a5e661af964e21408381d7e06c34d1608921aabdaf1c905736e7c69b994979f2","source_id":"us-cfr","stale":true,"prev":"us/10-cfr-434.512","next":"us/10-cfr-434.514"},"notice":"GroundRules: Original legal text. Not legal advice."}