{"data":{"id":"us/30-cfr-77.807-2","jurisdiction":"us","citation":"30 CFR 77.807-2","heading":"-2 Booms and masts; minimum distance from high-voltage lines.","body":"The booms and masts of equipment operated on the surface of any coal mine shall not be operated within 10 feet of an energized overhead powerline. Where the voltage of overhead powerlines is 69,000 volts, or more, the minimum distance from the boom or mast shall be as follows:\nNominal power line voltage (in 1,000 volts) Minimum distance (feet)\n69 to 114 12\n115 to 229 15\n230 to 344 20\n345 to 499 25\n500 or more 35","path":["Title 30—Mineral Resources","CHAPTER I—MINE SAFETY AND HEALTH ADMINISTRATION, DEPARTMENT OF LABOR","SUBCHAPTER O—COAL MINE SAFETY AND HEALTH","PART 77—MANDATORY SAFETY STANDARDS, SURFACE COAL MINES AND SURFACE WORK AREAS OF UNDERGROUND COAL MINES","Subpart I—Surface High-Voltage Distribution"],"source_url":"https://www.ecfr.gov/api/versioner/v1/full/2026-08-25/title-30.xml","current_through":"2026-08-25","vintage":"","retrieved_at":"2026-08-27T02:25:24Z","sha256":"d248d31eb43f8f6e6132297ccd11186513d1d28576b0bcc6a7e7843e3cced6fd","source_id":"us-cfr","stale":true,"prev":"us/30-cfr-77.807-1","next":"us/30-cfr-77.807-3"},"notice":"GroundRules: Original legal text. Not legal advice."}