{"data":{"id":"us/33-cfr-127.1507","jurisdiction":"us","citation":"33 CFR 127.1507","heading":"Water systems for fire protection.","body":"(a) Each waterfront facility handling LHG must have a supply of water and a means for distributing and applying the water to protect personnel; to cool storage tanks, equipment, piping, and vessels; and to control unignited leaks and spills in the marine transfer area for LHG except when the evaluation required by § 127.1501(a) indicates otherwise. The evaluation must address fire protection for structures, cargo, and vessels. Each water system must include on the pier or wharf at least one 2 1/2-inch supply line, one 2 1/2-inch fire hydrant, and enough 2 1/2-inch hose to connect the hydrant to the vessel.\n(b) Each water system must fully and simultaneously supply, for at least 2 hours, all fixed fire-protection systems, including monitor nozzles, at their designed flow and pressure for the worst single incident foreseeable, plus 63 L/s (1000 gpm) for streams from hand-held hoses.","path":["Title 33—Navigation and Navigable Waters","CHAPTER I—COAST GUARD, DEPARTMENT OF HOMELAND SECURITY","SUBCHAPTER L—WATERFRONT FACILITIES","PART 127—WATERFRONT FACILITIES HANDLING LIQUEFIED NATURAL GAS AND LIQUEFIED HAZARDOUS GAS","Subpart C—Waterfront Facilities Handling Liquefied Hazardous Gas"],"source_url":"https://www.ecfr.gov/api/versioner/v1/full/2026-08-25/title-33.xml","current_through":"2026-08-25","vintage":"","retrieved_at":"2026-08-27T02:25:35Z","sha256":"ac7f9eed9182c569d1a7b0ea9a27367cc4f783fa92e0d612e976ea45de57763e","source_id":"us-cfr","stale":true,"prev":"us/33-cfr-127.1505","next":"us/33-cfr-127.1509"},"notice":"GroundRules: Original legal text. Not legal advice."}