{"data":{"id":"us/33-cfr-149.660","jurisdiction":"us","citation":"33 CFR 149.660","heading":"What are the requirements for emergency power?","body":"(a) Each pumping platform complex must have emergency power equipment including a power source, associated transforming equipment, and a switchboard to provide power to simultaneously operate all of the following for a continuous period of 18 hours:\n(1) Emergency lighting circuits;\n(2) Aids to navigation equipment;\n(3) Communications equipment;\n(4) Radar equipment;\n(5) Alarm systems;\n(6) Electrically operated fire pumps; and\n(7) Other electrical equipment identified as emergency equipment in the operations manual for the deepwater port.\n(b) The equipment required by paragraph (a) of this section must:\n(1) All be located in the same space; and\n(2) Contain only machinery and equipment for the supply of emergency power (i.e., no oil or natural gas transfer pumping equipment) in accordance with 46 CFR 112.05.","path":["Title 33—Navigation and Navigable Waters","CHAPTER I—COAST GUARD, DEPARTMENT OF HOMELAND SECURITY","SUBCHAPTER NN—DEEPWATER PORTS","PART 149—DEEPWATER PORTS: DESIGN, CONSTRUCTION, AND EQUIPMENT","Subpart F—Design and Equipment"],"source_url":"https://www.ecfr.gov/api/versioner/v1/full/2026-08-25/title-33.xml","current_through":"2026-08-25","vintage":"","retrieved_at":"2026-08-27T02:25:35Z","sha256":"7c8ded451ecbf0039f3bce1995995b98b0ac2543cd4868b487ca1ddc72ba8f41","source_id":"us-cfr","stale":true,"prev":"us/33-cfr-149.655","next":"us/33-cfr-149.665"},"notice":"GroundRules: Original legal text. Not legal advice."}