{"data":{"id":"us/40-cfr-table-1b-to-subpart-ce-of-part-60","jurisdiction":"us","citation":"40 CFR Table 1B to Subpart Ce of Part 60","heading":"Table 1B to Subpart Ce of Part 60—Emissions Limits for Small, Medium, and Large HMIWI at Designated Facilities as Defined in § 60.32e(a)(1) and (a)(2)","body":"Pollutant Units (7 percent oxygen, dry basis) Emissions limits Averaging time 1 Method for demonstrating compliance 2\nHMIWI size\nSmall Medium Large\nParticulate matter Milligrams per dry standard cubic meter (mg/dscm) (grains per dry standard cubic foot (gr/dscf)) 66 (0.029) 46 (0.020) 25 (0.011) 3-run average (1-hour minimum sample time per run) EPA Reference Method 5 of appendix A-3 of part 60, or EPA Reference Method 26A or 29 of appendix A-8 of part 60.\nCarbon monoxide Parts per million by volume (ppmv) 20 5.5 11 3-run average (1-hour minimum sample time per run) EPA Reference Method 10 or 10B of appendix A-4 of part 60.\nDioxins/furans Nanograms per dry standard cubic meter total dioxins/furans (ng/dscm) (grains per billion dry standard cubic feet (gr/109 dscf)) or ng/dscm TEQ (gr/109 dscf) 16 (7.0) or 0.013 (0.0057) 0.85 (0.37) or 0.020 (0.0087) 9.3 (4.1) or 0.054 (0.024) 3-run average (4-hour minimum sample time per run) EPA Reference Method 23 of appendix A-7 of part 60.\nHydrogen chloride ppmv 44 7.7 6.6 3-run average (1-hour minimum sample time per run) EPA Reference Method 26 or 26A of appendix A-8 of part 60.\nSulfur dioxide ppmv 4.2 4.2 9.0 3-run average (1-hour minimum sample time per run) EPA Reference Method 6 or 6C of appendix A-4 of part 60.\nNitrogen oxides ppmv 190 190 140 3-run average (1-hour minimum sample time per run) EPA Reference Method 7 or 7E of appendix A-4 of part 60.\nLead mg/dscm (grains per thousand dry standard cubic feet (gr/103 dscf)) 0.31 (0.14) 0.018 (0.0079) 0.036 (0.016) 3-run average (1-hour minimum sample time per run) EPA Reference Method 29 of appendix A-8 of part 60.\nCadmium mg/dscm (gr/103 dscf) 0.017 (0.0074) 0.013 (0.0057) 0.0092 (0.0040) 3-run average (1-hour minimum sample time per run) EPA Reference Method 29 of appendix A-8 of part 60.\nMercury mg/dscm (gr/103 dscf) 0.014 (0.0061) 0.025 (0.011) 0.018 (0.0079) 3-run average (1-hour minimum sample time per run) EPA Reference Method 29 of appendix A-8 of part 60.\n1 Except as allowed under § 60.56c(c) for HMIWI equipped with CEMS.\n2 Does not include CEMS and approved alternative non-EPA test methods allowed under § 60.56c(b).","path":["Title 40—Protection of Environment","CHAPTER I—ENVIRONMENTAL PROTECTION AGENCY","SUBCHAPTER C—AIR PROGRAMS","PART 60—STANDARDS OF PERFORMANCE FOR NEW STATIONARY SOURCES","Subpart Ce—Emission Guidelines and Compliance Times for Hospital/Medical/Infectious Waste Incinerators"],"source_url":"https://www.ecfr.gov/api/versioner/v1/full/2026-08-25/title-40.xml","current_through":"2026-08-25","vintage":"","retrieved_at":"2026-08-27T02:26:04Z","sha256":"95d2c6ef8c72839a914550b2e12c524ff280e7d5a48861fee4c01d8bac541fc7","source_id":"us-cfr","stale":true,"prev":"us/40-cfr-table-1a-to-subpart-ce-of-part-60","next":"us/40-cfr-table-2a-to-subpart-ce-of-part-60"},"notice":"GroundRules: Original legal text. Not legal advice."}