{"data":{"id":"us/40-cfr-table-2-to-subpart-vvvv","jurisdiction":"us","citation":"40 CFR Table 2 to Subpart VVVV","heading":"Table 2 to Subpart VVVV—Emission Limitations for New Large Municipal Waste Combustors","body":"For the air pollutant If your affected facility is a new large municipal waste combustor, you must meet this emission limit, corrected to 7 percent oxygen a\nParticulate matter 5.1 mg/dscm.\nOpacity 10 percent opacity (6-minute block average).\nCadmium 2.3 ug/dscm.\nLead 23 ug/dscm.\nMercury 32 ug/dscm or 85 percent reduction by weight.\nSulfur dioxide 14 parts per million by volume dry basis or 79 percent reduction by weight or volume (daily 24-hour geometric average).\nHydrogen chloride 7.2 parts per million by volume dry basis or 98 percent reduction by weight or volume.\nDioxins/furans 11 nanograms per dry standard cubic meter (total mass).\nNitrogen oxides 50 parts per million by volume dry basis (daily 24-hour arithmetic average).\na Measured at the combustor outlet in conjunction with a measurement of oxygen concentration. CEMS data during warmup, startup, and shutdown, as defined in this subpart, are not corrected to 7 percent oxygen, and are used as measured. The averaging times are specified in greater detail in § 60.5940.","path":["Title 40—Protection of Environment","CHAPTER I—ENVIRONMENTAL PROTECTION AGENCY","SUBCHAPTER C—AIR PROGRAMS","PART 60—STANDARDS OF PERFORMANCE FOR NEW STATIONARY SOURCES","Subpart VVVV—Standards of Performance for Large Municipal Waste Combustors"],"source_url":"https://www.ecfr.gov/api/versioner/v1/full/2026-08-25/title-40.xml","current_through":"2026-08-25","vintage":"","retrieved_at":"2026-08-27T02:26:04Z","sha256":"c37a5d15b06b73463c13bbf72d94d51f271c3d0da73a710252ae53246950529e","source_id":"us-cfr","stale":true,"prev":"us/40-cfr-table-1-to-subpart-vvvv","next":"us/40-cfr-table-3-to-subpart-vvvv-of-part-60"},"notice":"GroundRules: Original legal text. Not legal advice."}