{"data":{"id":"us/40-cfr-table-2a-to-subpart-ce-of-part-60","jurisdiction":"us","citation":"40 CFR Table 2A to Subpart Ce of Part 60","heading":"Table 2A to Subpart Ce of Part 60—Emissions Limits for Small HMIWI Which Meet the Criteria Under § 60.33e(b)(1)","body":"Pollutant Units (7 percent oxygen, dry basis) HMIWI emissions limits Averaging time 1 Method for demonstrating compliance 2\nParticulate matter mg/dscm (gr/dscf) 197 (0.086) 3-run average (1-hour minimum sample time per run) EPA Reference Method 5 of appendix A-3 of part 60, or EPA Reference Method 26A or 29 of appendix A-8 of part 60.\nCarbon monoxide ppmv 40 3-run average (1-hour minimum sample time per run) EPA Reference Method 10 or 10B of appendix A-4 of part 60.\nDioxins/furans ng/dscm total dioxins/furans (gr/109 dscf) or ng/dscm TEQ (gr/109 dscf) 800 (350) or 15 (6.6) 3-run average (4-hour minimum sample time per run) EPA Reference Method 23 of appendix A-7 of part 60.\nHydrogen chloride ppmv 3,100 3-run average (1-hour minimum sample time per run) EPA Reference Method 26 or 26A of appendix A-8 of part 60.\nSulfur dioxide ppmv 55 3-run average (1-hour minimum sample time per run) EPA Reference Method 6 or 6C of appendix A-4 of part 60.\nNitrogen oxides ppmv 250 3-run average (1-hour minimum sample time per run) EPA Reference Method 7 or 7E of appendix A-4 of part 60.\nLead mg/dscm (gr/103 dscf) 10 (4.4) 3-run average (1-hour minimum sample time per run) EPA Reference Method 29 of appendix A-8 of part 60.\nCadmium mg/dscm (gr/103 dscf) 4 (1.7) 3-run average (1-hour minimum sample time per run) EPA Reference Method 29 of appendix A-8 of part 60.\nMercury mg/dscm (gr/103 dscf) 7.5 (3.3) 3-run average (1-hour minimum sample time per run) EPA Reference Method 29 of appendix A-8 of part 60.\n1 Except as allowed under § 60.56c(c) for HMIWI equipped with CEMS.\n2 Does not include CEMS and approved alternative non-EPA test methods allowed under § 60.56c(b).","path":["Title 40—Protection of Environment","CHAPTER I—ENVIRONMENTAL PROTECTION AGENCY","SUBCHAPTER C—AIR PROGRAMS","PART 60—STANDARDS OF PERFORMANCE FOR NEW STATIONARY SOURCES","Subpart Ce—Emission Guidelines and Compliance Times for Hospital/Medical/Infectious Waste Incinerators"],"source_url":"https://www.ecfr.gov/api/versioner/v1/full/2026-08-25/title-40.xml","current_through":"2026-08-25","vintage":"","retrieved_at":"2026-08-27T02:26:04Z","sha256":"72e4dbf56c387dc3edd41025e426250586baed6926fb8b12aabc07170afc0390","source_id":"us-cfr","stale":true,"prev":"us/40-cfr-table-1b-to-subpart-ce-of-part-60","next":"us/40-cfr-table-2b-to-subpart-ce-of-part-60"},"notice":"GroundRules: Original legal text. Not legal advice."}