{"data":{"id":"us/40-cfr-table-3-to-subpart-fff-of-part-62","jurisdiction":"us","citation":"40 CFR Table 3 to Subpart FFF of Part 62","heading":"Table 3 to Subpart FFF of Part 62—Municipal Waste Combustor Operating Requirements","body":"Municipal waste combustor technology Carbon monoxide emissions level (parts per million by volume) a Averaging time (hrs) b\nMass burn waterwall 100 4\nMass burn refractory 100 4\nMass burn rotary refractory 100 24\nMass burn rotary waterwall 250 24\nModular starved air 50 4\nModular excess air 50 4\nRefuse-derived fuel stoker 200 24\nFluidized bed, mixed fuel (wood/refuse-derived fuel) 200 c 24\nBubbling fluidized bed combustor 100 4\nCirculating fluidized bed combustor 100 4\nPulverized coal/refuse-derived fuel mixed fuel-fired combustor 150 4\nSpreader stoker coal/refuse-derived fuel mixed fuel-fired combustor 200 24\na Measured at the combustor outlet in conjunction with a measurement of oxygen concentration, corrected to 7 percent oxygen, dry basis. Calculated as an arithmetic average.\nb Averaging times are 4-hour or 24-hour block averages.\nc 24-hour block average, geometric mean.","path":["Title 40—Protection of Environment","CHAPTER I—ENVIRONMENTAL PROTECTION AGENCY","SUBCHAPTER C—AIR PROGRAMS","PART 62—APPROVAL AND PROMULGATION OF STATE PLANS FOR DESIGNATED FACILITIES AND POLLUTANTS","Subpart FFF—Federal Plan Requirements for Large Municipal Waste Combustors Constructed on or Before September 20, 1994"],"source_url":"https://www.ecfr.gov/api/versioner/v1/full/2026-08-25/title-40.xml","current_through":"2026-08-25","vintage":"","retrieved_at":"2026-08-27T02:26:04Z","sha256":"0db183ace1f52d2da77c8a9f0a2ffec0949dd8e678f44c5239878ba15e07be21","source_id":"us-cfr","stale":true,"prev":"us/40-cfr-table-2-to-subpart-fff-of-part-62","next":"us/40-cfr-table-4-to-subpart-fff-of-part-62"},"notice":"GroundRules: Original legal text. Not legal advice."}
