{"data":{"id":"us/40-cfr-table-3-to-subpart-iiii-of-part-60","jurisdiction":"us","citation":"40 CFR Table 3 to Subpart IIII of Part 60","heading":"Table 3 to Subpart IIII of Part 60—Certification Requirements for Stationary Fire Pump Engines","body":"As stated in § 60.4202(d), you must certify new stationary fire pump engines beginning with the following model years:\nEngine power Starting model year engine manufacturers must certify new stationary fire pump engines according to § 60.4202(d)1\nKW\u003c75 (HP\u003c100) 2011\n75≤KW\u003c130 (100≤HP\u003c175) 2010\n130≤KW≤560 (175≤HP≤750) 2009\nKW\u003e560 (HP\u003e750) 2008\n1 Manufacturers of fire pump stationary CI ICE with a maximum engine power greater than or equal to 37 kW (50 HP) and less than 450 KW (600 HP) and a rated speed of greater than 2,650 revolutions per minute (rpm) are not required to certify such engines until three model years following the model year indicated in this Table 3 for engines in the applicable engine power category.","path":["Title 40—Protection of Environment","CHAPTER I—ENVIRONMENTAL PROTECTION AGENCY","SUBCHAPTER C—AIR PROGRAMS","PART 60—STANDARDS OF PERFORMANCE FOR NEW STATIONARY SOURCES","Subpart IIII—Standards of Performance for Stationary Compression Ignition Internal Combustion Engines"],"source_url":"https://www.ecfr.gov/api/versioner/v1/full/2026-08-25/title-40.xml","current_through":"2026-08-25","vintage":"","retrieved_at":"2026-08-27T02:26:04Z","sha256":"38946b2b24c74ec3d708b1360cef93da6f7964f2d8182122504ea66e4bac6754","source_id":"us-cfr","stale":true,"prev":"us/40-cfr-table-2-to-subpart-iiii-of-part-60","next":"us/40-cfr-table-4-to-subpart-iiii-of-part-60"},"notice":"GroundRules: Original legal text. Not legal advice."}