{"data":{"id":"us/40-cfr-table-6-to-subpart-iiii-of-part-60","jurisdiction":"us","citation":"40 CFR Table 6 to Subpart IIII of Part 60","heading":"Table 6 to Subpart IIII of Part 60—Optional 3-Mode Test Cycle for Stationary Fire Pump Engines","body":"[As stated in § 60.4210(g), manufacturers of fire pump engines may use the following test cycle for testing fire pump engines:]\nMode No. Engine speed 1 Torque (percent) 2 Weighting factors\n1 Rated 100 0.30\n2 Rated 75 0.50\n3 Rated 50 0.20\n1 Engine speed: ±2 percent of point.\n2 Torque: NFPA certified nameplate HP for 100 percent point. All points should be ±2 percent of engine percent load value.","path":["Title 40—Protection of Environment","CHAPTER I—ENVIRONMENTAL PROTECTION AGENCY","SUBCHAPTER C—AIR PROGRAMS","PART 60—STANDARDS OF PERFORMANCE FOR NEW STATIONARY SOURCES","Subpart IIII—Standards of Performance for Stationary Compression Ignition Internal Combustion Engines"],"source_url":"https://www.ecfr.gov/api/versioner/v1/full/2026-08-25/title-40.xml","current_through":"2026-08-25","vintage":"","retrieved_at":"2026-08-27T02:26:04Z","sha256":"e3e80baed67cfb7f479416a3634d224818e2f128e069b4e4c23e3d2ca91f096a","source_id":"us-cfr","stale":true,"prev":"us/40-cfr-table-5-to-subpart-iiii-of-part-60","next":"us/40-cfr-table-7-to-subpart-iiii-of-part-60"},"notice":"GroundRules: Original legal text. Not legal advice."}