{"data":{"id":"us/46-cfr-108.445","jurisdiction":"us","citation":"46 CFR 108.445","heading":"Alarm and means of escape.","body":"(a) Each CO2 system that has a supply of more than 136 kilograms (300 pounds) of CO2, except a system that protects a tank, must have an alarm that sounds for at least 20 seconds before the CO2 is released into the space.\n(b) Each audible alarm for a CO2 system must have the CO2 supply for the system as its source of power and must be in a visible location in the spaces protected.","path":["Title 46—Shipping","CHAPTER I—COAST GUARD, DEPARTMENT OF HOMELAND SECURITY","SUBCHAPTER I-A—MOBILE OFFSHORE DRILLING UNITS","PART 108—DESIGN AND EQUIPMENT","Subpart D—Fire Extinguishing Systems"],"source_url":"https://www.ecfr.gov/api/versioner/v1/full/2026-08-25/title-46.xml","current_through":"2026-08-25","vintage":"","retrieved_at":"2026-08-27T02:26:22Z","sha256":"904eac7c521118c2329904d9afe615ebfc0b7158e7182cb90990a0f61b431b4e","source_id":"us-cfr","stale":true,"prev":"us/46-cfr-108.444","next":"us/46-cfr-108.446"},"notice":"GroundRules: Original legal text. Not legal advice."}