{"data":{"id":"us/46-cfr-108.467","jurisdiction":"us","citation":"46 CFR 108.467","heading":"Water supply.","body":"The water supply of a foam extinguishing system must not be the water supply of the fire main system on the unit unless when both systems are operated simultaneously—\n(a) The water supply rate to the foam production equipment meets the requirements of this section; and\n(b) Water supply rate to the fire hydrants required by § 108.415 of this subpart allows compliance with the pressure requirement in that section.","path":["Title 46—Shipping","CHAPTER I—COAST GUARD, DEPARTMENT OF HOMELAND SECURITY","SUBCHAPTER I-A—MOBILE OFFSHORE DRILLING UNITS","PART 108—DESIGN AND EQUIPMENT","Subpart D—Fire Extinguishing Systems"],"source_url":"https://www.ecfr.gov/api/versioner/v1/full/2026-08-25/title-46.xml","current_through":"2026-08-25","vintage":"","retrieved_at":"2026-08-27T02:26:22Z","sha256":"0113292eb36405a6240ef985aafece1ea8c79657ce5eaddb81e69be9a25b2bc4","source_id":"us-cfr","stale":true,"prev":"us/46-cfr-108.463","next":"us/46-cfr-108.469"},"notice":"GroundRules: Original legal text. Not legal advice."}