{"data":{"id":"us/46-cfr-111.05-29","jurisdiction":"us","citation":"46 CFR 111.05-29","heading":"-29 Dual voltage direct current systems.","body":"Each dual voltage direct current system must have a suitably sensitive ground detection system which indicates current in the ground connection, has a range of at least 150 percent of neutral current rating and indicates the polarity of the fault.\nGrounded Conductors","path":["Title 46—Shipping","CHAPTER I—COAST GUARD, DEPARTMENT OF HOMELAND SECURITY","SUBCHAPTER J—ELECTRICAL ENGINEERING","PART 111—ELECTRIC SYSTEMS—GENERAL REQUIREMENTS","Subpart 111.05—Equipment Ground, Ground Detection, and Grounded Systems"],"source_url":"https://www.ecfr.gov/api/versioner/v1/full/2026-08-25/title-46.xml","current_through":"2026-08-25","vintage":"","retrieved_at":"2026-08-27T02:26:22Z","sha256":"8401a62bb34ef5ab72dd02d7908438fb262e5494ccec005e00f8e3cf7615383c","source_id":"us-cfr","stale":true,"prev":"us/46-cfr-111.05-27","next":"us/46-cfr-111.05-31"},"notice":"GroundRules: Original legal text. Not legal advice."}