{"data":{"id":"us/46-cfr-111.30-4","jurisdiction":"us","citation":"46 CFR 111.30-4","heading":"-4 Circuit breakers removable from the front.","body":"Circuit breakers, when installed on generator or distribution switchboards, must be mounted or arranged in such a manner that the circuit breaker may be removed from the front without unbolting bus or cable connections or deenergizing the supply, unless the switchboard is divided into sections, such that each section is capable of providing power to maintain the vessel in a navigable condition, and meets § 111.30-24 (a) and (b).","path":["Title 46—Shipping","CHAPTER I—COAST GUARD, DEPARTMENT OF HOMELAND SECURITY","SUBCHAPTER J—ELECTRICAL ENGINEERING","PART 111—ELECTRIC SYSTEMS—GENERAL REQUIREMENTS","Subpart 111.30—Switchboards"],"source_url":"https://www.ecfr.gov/api/versioner/v1/full/2026-08-25/title-46.xml","current_through":"2026-08-25","vintage":"","retrieved_at":"2026-08-27T02:26:22Z","sha256":"dd2fb3805f2b56e2c14fbcc48b8e10cd57c112978217dd189441eb6ff2dd2a8d","source_id":"us-cfr","stale":true,"prev":"us/46-cfr-111.30-3","next":"us/46-cfr-111.30-5"},"notice":"GroundRules: Original legal text. Not legal advice."}