{"data":{"id":"us/46-cfr-111.40-15","jurisdiction":"us","citation":"46 CFR 111.40-15","heading":"-15 Overcurrent device.","body":"The total load on any overcurrent device located in a panelboard must not exceed 80 percent of its rating if, in normal operation, the load will continue for 3 hours or more; except if the assembly, including the overcurrent device, is rated for continuous duty at 100% of its rating.","path":["Title 46—Shipping","CHAPTER I—COAST GUARD, DEPARTMENT OF HOMELAND SECURITY","SUBCHAPTER J—ELECTRICAL ENGINEERING","PART 111—ELECTRIC SYSTEMS—GENERAL REQUIREMENTS","Subpart 111.40—Panelboards"],"source_url":"https://www.ecfr.gov/api/versioner/v1/full/2026-08-25/title-46.xml","current_through":"2026-08-25","vintage":"","retrieved_at":"2026-08-27T02:26:22Z","sha256":"f363dc30607fdf22d12f63f8b3e4ffd4d2316eddc2349d259bacf3173e280187","source_id":"us-cfr","stale":true,"prev":"us/46-cfr-111.40-13","next":"us/46-cfr-111.50-1"},"notice":"GroundRules: Original legal text. Not legal advice."}